Laminar Flow Modules

Air Handling / Laminar Modules

Laminar Flow Modules

Laminar Flow Modules


Housings

The filter housing and plenum shall be fabricated from 16 gauge steel, reinforced and braced for rigidity. Housing shall be furnished with suspension support fittings to receive 3/8” threaded rod hangers supplied by others.

The fan cabinet shall be fabricated from 16 gauge steel depending on the configuration. Fan cabinet shall be furnished with minimum four (4) suspension support fittings to receive 3/8” threaded rod hangers supplied by others.

Housings shall be finished with a white protective enamel and sealed at all joints in the positive pressure area with a silicone sealant.

Insulation

All interior surfaces of cabinet shall be acoustically lined with a non-shedding insulation and secured with adhesive. All exposed edges and joints shall be sealed to prevent fraying.

Blowers

Blower shall be belt driven, forward curved centrifugal type, dynamically balanced and tested prior to being installed within cabinet.

Bearings shall be sealed ball type with locking collar.

Steel shaft shall be provided with flats for blowers and keyway to secure driven pulley.

Motor

Open drip proof 60 hz motor mounted on an adjustable slide base with rubber isolators. Thermally protected and fused motor is rated for continuous duty. Standard voltage is 115 with optional 208/230V and 460/480V.

Drive pulley shall be adjustable to allow speed ratio variations of up to 30 percent. Drive belt shall be of a non-static generating type V-belt and rated at 150 percent of motor horsepower.

Access:
An access panel shall be installed in the Motor/Blower housing to serve the blower, motor drives and electrical connections.


HEPA Filters

Multiple Gel Seal Style HEPA filters have rated efficiency standard of 99.99% at 0.3 micron. Each filter has an initial pressure drop not to exceed .5” W.G. at 800 CFM rated air flow. An access port with removable plug located in the center of each filter element face is provided for introducing an upstream challenge or measuring static pressure. HEPA filters are replaceable from roomside.

Prefilters

Removable prefilters having an efficiency rating of 30 percent ASHRAE shall be installed on the air intake opening. Prefilters and eggcrate face grilles are held in place by a removable retaining strip.

Grilles

HEPA filters are protected by eggcrate grilles.

Electrical

CRI provides an ON/OFF switch and junction box located inside the fan cabinet for connecting to the building power source. Electrical connections to building power source shall be done on site by a qualified electrician at buyers cost.


Technical Drawings

Technical Drawings

Vertical Flow LFM

Horizontal Flow LFM

Suspended Vertical Flow LFM w/Gowning Area

Standard

Option A

Option B

Option C


Size, CFM and Filter Schedule

Model

Size

Nominal Filter Area Sq. Ft.

HEPA’s

No. Prefilters

CFM

H.P.*

Dimensions (A, B, C, D)

176404

4 x 4

16

2

2

1600

.5 – .75

4′ 4′ 20″ 44″

176406

4 x 6

24

3

2

2400

.75 – 1

6′ 4′ 20″ 44″

176408

4 x 8

32

4

2

3200

.75 – 1

8′ 4′ 20″ 44″

176410

4 x 10

40

5

2

4000

1 – 1.5

10′ 4′ 20″ 44″

176412

4 x 12

48

6

2

4800

1.5 – 2

12′ 4′ 20″ 47″

176604

6 x 4

24

2

3

2400

.75 – 1

4′ 6′ 20″ 44″

176606

6 x 6

36

3

3

3600

1 – 1.5

6′ 6′ 20″ 44″

176608

6 x 8

48

4

3

4800

1.5 – 2

8′ 6′ 20″ 44″

176610

6 x 10

60

5

3

6000

2 – 3

10′ 6′ 20″ 44″

176612

6 x 12

72

6

3

7200

2 – 3

12′ 6′ 20″ 47″

 

* HP based on .7 “TSP” W.G.

 


Light Options

Light Options

Light Option A

Light Option B

Light Option C


Additional Options

Additional Options

Stainless Steel Construction

ULPA Filter 99.9995% eff. @ 0.12 micron or larger

Vinyl Curtains, Regular or Anti-Static

Control Panel, Static Control

Magnehelic Gage


Built to Order

Built to Order

Suspended Vertical Flow LFM w/ End Fan, Bottom Inlet and Curtain Enclosure

Horizontal Flow LFM Front Inlet w/ Hood and Light

Suspended Vertical Flow LFM (Top Fan)

Horizontal Flow LFM w/ Back Inlet

Horizontal Flow LFM w/ Front Inlet

Suspended Vertical Flow LFM (End Fan Back Inlet)

Horizontal Flow LFM w/ Enclosure and Strip Door

Suspended Vertical Flow LFM w/ Gowning Area (Top Fan)


Clean Rooms International, Inc

4939 Starr St SE
Grand Rapids, MI 49546

Terms and conditions

Contact us

Toll-free: 877–380–1860

Phone: 616–452–8700

Fax: 616–452–2372

Email: sales@cleanroomsint.com

Terms and conditions

©2021 Clean Rooms International, Inc