GS

Terminal Diffuser

GS

GS

Key Features


  • Gel Seal Style HEPA or ULPA Filter
  • Replaceable From Roomside


GS Style Filter Data

The gel seal style HEPA Filter is designed for 90 FPM average face velocity @ Initial 0.47 w.g and has a rated efficiency of 99.99% @ 0.3 micron or larger.

An anodized aluminum frame holds the 53mm media which is protected by a diamond pattern white epoxy coated steel grille. Final filters are replaceable from roomside.

Filter Dimensions

20-5/8″ x 20-5/8″ x 3″ for 2×2 units and 20-5/8″ x 44-5/8″ x 3″ for 2×4 units.

Access Port

Centerboard with access port for disc adjustment.

Options

ULPA Filter, thermal insulation, and a range of grille options.


GS Terminal Diffusers are ideal for pharmaceutical companies, manufacturers of medical devices and companies in highly regulated industries. The GS series feature a gel channel on the upstream side of  the final filter which provides a leak-free seal between the filter and the housing.

GS Terminal Diffusers feature a HEPA or ULPA filter replaceable from roomside while the filter housing remains in place.

The white powdercoated housing, fabricated from 20 gauge steel, is positively sealed to a hood fabricated from galvanized steel.

A 10″ or 12″ diameter inlet collar at the center of the filter hood allows for simple field connection to the main air supply using flexible duct.

The damper assembly is adjustable from within the room and is supported by a damper support channel permanently attached to the filter hood duct collar. A perforated damper disc is mounted on threaded rod and a guide provides screwdriver adjustments of the damper assembly from roomside.

Final filters are protected with a white epoxy diamond pattern grille and are tested according to accepted procedures as described by the Institute of Environmental Sciences (IEST)   and/or ISO standards. The standard HEPA filter is 99.99% efficient and an ULPA grade 99.9995% efficient filter is available as an option.

A polystyrene eggcrate grille in an anodized aluminum frame is hinged to open, permitting removal of the filter without removing the unit from the ceiling. Optional perforated stainless steel or aluminum grilles are available.


Technical Drawings

Technical Drawings

GS 2 x 2—Swing Down Grille Allows Easy Access To Filter

GS 2 x 4—Exploded View

Optional Thermal Insulation

Gel Seal Channel-Section View

Filter Clamp Detail

Radial Diffuser Grille


Ordering Information

Mfg. Code

Nominal Size

Filter Size (In)

Inlet Collar

Efficiency

Weight

11104

2 x 2

20.62 x 20.62 x 3

10

99.99% @ 0.3

33 lbs.

11105

2 x 2

20.62 x 20.62 x 3

12

99.99% @ 0.3

33 lbs.

11106

2 x 4

20.62 x 44.62 x 3

10

99.99% @ 0.3

57 lbs.

11107

2 x 4

20.62 x 44.62 x 3

12

99.99% @ 0.3

57 lbs.


Optional Thermal Insulation

Optional Thermal Insulation

19004 2 x 2 Insulation Blanket, 1.5” Foil

302204 2 x 2 ULPA Gel Seal Filter

19005 2 x 4 Insulation Blanket, 1.5” Foil

302203 2 x 4 ULPA Gel Seal Filter


Replacement Filters

Model

HEPA

Efficiency

ULPA

Efficiency

2 x 2 Units

302201

99.99% @ 0.3

302204

99.9995% @ 0.12

2 x 4 Units

302200

99.99% @ 0.3

302203

99.9995% @ 0.12



Related products (4)

Related products (4)

Grille Options (Additional Options)

GS LI

Final Filters

Sheet Rock Adapters & Ceiling Collars

Clean Rooms International, Inc

4939 Starr St SE
Grand Rapids, MI 49546

Terms and conditions

Contact us

Toll-free: 877–380–1860

Phone: 616–452–8700

Fax: 616–452–2372

Email: sales@cleanroomsint.com